THE EFFECT OF THE WINDOW-TO-WALL RATIO ON COOLING ENERGY USAGE AND COMFORT TEMPERATURE

Budhiyanto, Aris (2018) THE EFFECT OF THE WINDOW-TO-WALL RATIO ON COOLING ENERGY USAGE AND COMFORT TEMPERATURE. DIMENSI - Journal of Architecture and Built Environment, 44 (2). pp. 189-194. ISSN 0126-219X

[thumbnail of Publikasi1_17008_3908.pdf] PDF
Publikasi1_17008_3908.pdf

Download (471kB)
[thumbnail of peerreview]
Preview
PDF (peerreview)
peerreview_1.pdf

Download (731kB)
[thumbnail of cek plagiasi]
Preview
PDF (cek plagiasi)
cek_plagiat.pdf

Download (93kB)

Abstract

This study presents an investigation of the effect of building envelope, especially glass facade buildings on cooling energy usage and thermal comfort. An office building was modeled with various window-to-wall ratio (WWR) using panasap glass with SC=0.58 in order to analyze the effect of the WWR addition on cooling energy usage and comfort
temperature. The result suggested that the average increase of the cooling energy usage is about 5.67% per 10% WWR addition, and of the operative temperature ranges from 0.350C to 0.560C per 10% WWR addition. Moreover, the building
with above 20% WWR doesn’t provide comfort temperature.